Viewing inquiries for 06-0U2304

Submit new inquiry for this project


Inquiry #1: What dates will the pump stations be allowed to be shut down?
Inquiry submitted 03/25/2020

Response #1:Submitted for consideration.
Response posted 03/25/2020


Response #2:There are no shut down dates for the pump stations. Please see section 74-1.01C(5)(c). Please bid per the current contract documents.
Response posted 03/26/2020




Inquiry #2: Due to the COVID-19 Shelter in Place order requiring a reduction of our staff, Telstar Instruments is requesting an extension to this bid date. If possible, our request is to extend the bid due date to April 30, 2020.
Inquiry submitted 04/06/2020

Response #1:The Department is maintaining the current schedule for contracts bid opening this week. As the impacts of COVID-19 are dynamic, the Department will evaluate future Bid Openings on a weekly basis. The Department will update this information as the situation warrants.
Response posted 04/06/2020




Inquiry #3: Shape Inc. and I wish to submit to Cal Trans for pre-approval, the Flygt pump/motor selections for each of the ten (10) pump stations since the Flygt units that best meets the project documents design operating conditions vary in a number of significant ways from the Fairbanks pump/motor units that are noted. Some of the differences are in the following areas:
a) RPM
b) Nameplate Motor Horsepower - which ultimately might change the size of VFD"s and other electrical components in the pump system
e) pump's discharge / suction size
f) Type / design of the impeller being offered - the Flygt units will be fitted with the "N" impeller and have stationary cutter/relief groove insert plate with both components being constructed out of hard iron/high chrome. Solids size handling size of the impeller might not be a 3" sphere.
g) pump efficiency
h) noted design operating condition GPM @ TDH with motor nameplate HP - when reviewing the noted Fairbanks pump model / Motor HP demand being called out in the project documents, the stated performance requirements overloads the motor horsepower noted also in the documents.

Inquiry submitted 04/07/2020

Response #1:Submitted for consideration.
Response posted 04/08/2020


Response #2:Material can not be preapproved before contract award. Please see section 74-1.01C for submittal requirements. Please bid per the current contract documents.
Response posted 04/09/2020




Inquiry #4: 1. Please provide a specification for the ceiling surface mount fluorescent or LED fixtures shown on all Modified Electrical Plans. The plans and specifications do not show whether these fixtures are to be Fluorescent or LED nor do they provide the desired wattage or luminesce. They fixtures appear to be 48” x 12” scaled from the plans.

2. Please provide a specification for the surface wall mount sump light fixtures shown on the same drawings. The plans and specifications do not provide necessary details to quote the desired fixtures.

3. Please provide a specification for the surface wall mount Area Light for all (10) pump plant locations. The existing specifications and plans do not define the desired fixture.

Inquiry submitted 04/08/2020

Response #1:Submitted for consideration.
Response posted 04/08/2020


Response #2:Please see section 74-3.02G of the special provisions. Please bid per the current contract documents.
Response posted 04/08/2020




Inquiry #5: 1. MCC manufacturers for Avenue 24 require an additional 20” wide MCC section to provide the MCC with all the desired equipment. Will the room accommodate (3) 20” wide MCC sections? It appears that based on drawing EE10-3 that there is sufficient space.
Inquiry submitted 04/09/2020

Response #1:Submitted for consideration.
Response posted 04/10/2020


Response #2:Please see general note A on EE10-5. Please bid per the current contract documents.


Response posted 04/13/2020




Inquiry #6: 1. Special Provisions on page 22 under 74-3.02B(3) requires that a key interlock kit be installed for all circuit breakers that prohibit breaker operation when the key is removed. Please advise and confirm is a key interlock to be provided for all circuit breakers or only breakers powering starters or VFDs. No key interlocks are shown on the contract plans.
Inquiry submitted 04/13/2020

Response #1:Submitted for consideration.
Response posted 04/13/2020


Response #2:The key interlock in section 74-3.02B(3) Motor Control Center Equipment is only required for the breakers feeding the starters or VFDs.
Response posted 04/14/2020


The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.07, "JOB SITE AND DOCUMENT EXAMINATION" of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.