Inquiry #1: Section 14-11.17E requires to train, provide PPE and provide medical surveillance for 3 State employees. Please confirm that the extent of the medical surveillance for the State employees is restricted to monitoring on-site concerns and does not include the HAZWOPER Standards to provide baseline medical exam and exit medical exam with results needing to be kept on file for 30 years.
Inquiry submitted 02/17/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 02/17/2022


Response #2:Medical surveillance would be for on-site concerns if surveillance is required under the Health and Safety Plan, prepared by CIH. The project is not considered a HAZWOPER Site requiring the general construction standards 29 CFR 1926.65.
Response posted 03/17/2022




Inquiry #2: Are construction joints permitted in the pump plant wall construction?
Inquiry submitted 02/17/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 02/17/2022


Response #2:Please bid per the current contract documents.
Response posted 02/22/2022




Inquiry #3: What bid item is the Seal Course Concrete work incidental to and/or included with?
Inquiry submitted 02/17/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 02/18/2022


Response #2:Please refer to Item "Seal Course Concrete" listed in the "Quantities" list on Sheet 61/133, and the details on Sheets 69/133, 70/113, 71/133 and 72/113.
Response posted 02/22/2022




Inquiry #4: What bid item is the Structural Concrete Fill (Plain Concrete) work incidental to and/or included with?
Inquiry submitted 02/17/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 02/18/2022


Response #2:Please refer to "Structural Concrete (Plain Concrete)" listed in the "Quantities" list on Sheet 61/133, and the details on Sheets 69/133, 70/133 and 71/133.
Response posted 02/22/2022




Inquiry #5: Please provide the 3D CAD files for this project grading.
Inquiry submitted 03/03/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/03/2022


Response #2:Caltrans provides 3D CAD files, but not for this project.
Response posted 03/21/2022




Inquiry #6: For the RCP Pipe shown on the drainage plans please advise the class of pipe to be provided.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:For RCP class please refer to 2018 standard spec section 65-2.02C Circular Reinforced Concrete Pipe, describe or chosen by class.
Response posted 03/17/2022




Inquiry #7: Drawing DQ-1 indicates that the 57LF of abandoned pipe is to be filled with "6.63 CY of Sand Backfill". The item code for this bid item (710102) refers to specifications 71 which is for grouting. Please advise whether pipe is to be filled with sand or grout or whether it is up to the Contractor to decide.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:For Sand back fill and Grout use ,refer to specification section # 71-6.03C Construction.
Response posted 03/17/2022




Inquiry #8: There is a detail for a "Concrete Collar" on sheet DD-1. It does not appear concrete collars are required anywhere. Please confirm.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:D1 is provided standard details per District standard plans, concrete collar is not part of this contract plans, please use detail whichever will be needed.
Response posted 03/17/2022




Inquiry #9: There is a detail for a "Side Connection" on sheet DD-1 that appears to be for pipe connecting at an angle. There appears to be no locations where this detail is required. Please confirm.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:D1 is provided standard details per District standard plans, there are some connections which are not at 90 degree ,please use detail whichever will be needed.
Response posted 03/17/2022




Inquiry #10: There is a detail "Cap Inlet Detail" on sheet DD-1. There appears to be no locations where this detail is required. Please confirm.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:D1 is provided standard details per District standard plans, Cap Inlet is not part of this contract plans, please use detail whichever will be needed.
Response posted 03/17/2022




Inquiry #11: Drawing ST-1 and ST-27 show the "Equipment Access Grate". In it's final built condition the equipment access hatch is directly above the sump pump discharge pipe such that a scissor lift cannot be lowered into the pump station without first disassembling the pipe. This may provide a challenge for Caltrans for future maitenance should scissor lift access be needed to reach certain items in the plant. Is it possible to extend the "Equipment Access Grate" opening to the north by about 5' to 6' to allow easy unempeded access to lower a scissor lift into the hole should it be needed in the future. This will also help with ease of construction.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Please bid per current contract documents.
Response posted 03/17/2022




Inquiry #12: There is a detail for a "JC 3-C" on sheet DD-3. It does not appear this detail is used anywhere. Please confirm.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:D3 is provided standard details per District Standard plans, JC-3 C is not part of this contract plans, please use detail whichever will be needed.
Response posted 03/17/2022




Inquiry #13: Detail 1 on M-4 shows a layer of seal course concrete under the 24" Dia Steel Pipe. There is a dimension of 4'-0" from the bottom of the pipe to the bottom of the seal course concrete but no dimension to designate the thickness of the seal course concrete. Please provide the thickness of the seal course concrete.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Thickness of seal course concrete is 2 feet, please refer to addendum #2 issued on March 17, 2022 for more information.
Response posted 03/17/2022




Inquiry #14: Please advise if the on-site material can be used for backfill for the pump station, for jack and bore pits, for the underground pipe, for the inlets, and manholes, for the underground electrical work?
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Site soils cannot be used as backfill, please see section 14-11.11 for more information.
Response posted 03/17/2022




Inquiry #15: On sheet DP-1 the new 24" RCP pipe ties into the existing 24" RCP pipe at Sta 57+97.33. Please confirm the existing line is not live. Also, on sheet M-2 the new 24" welded steel pipe discharge line ties into the existing 24" welded steel pipe. Please also confirm the existing line is not live.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:
-24" RCP is live during rain event and may have standing water. End of the pipe is not capped but protected from soil intrusion.

-24" WSP is not live but may have standing water.
Response posted 03/17/2022




Inquiry #16: Specification 74-1.03E discusses maintenance of the pumps following completion. Please advise if this is really to be included in pricing and if so how long the maintenance period is to last.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Yes the maintenance must be provided and the maintenance must continue until contract acceptance. Please see section 74-1.01C(5)(c) and 74-1.03E. Please bid per current contract documents.
Response posted 03/17/2022




Inquiry #17: Specification 74-1.01D(2)(c) discusses performance testing, that however appears to be all the testing and commissioning mentioned. Please advise the extent of the testing and commissioning for the project. Are the pumps to be commissioned / start up so that they are put into live service or will the Caltrans take care of this.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Please see section 74-1.01D(2)(b) and section 74-1.01D(2)(c) for operational and performance test requirements as they are two separate tests. Please also see section 74-2.01C(3) for additional requirements.
Response posted 03/17/2022




Inquiry #18: Specification 74-1.01D(2)(c) discusses performance testing. Will Caltrans provide the water for this. Will water be able to be discharged through the new discharge line and the existing line connected to the new discharge line?
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:Contractor is responsible for supplying water for Operational and Performance Tests please refer to Section 74-1.01D(2)(b)
Response posted 03/17/2022




Inquiry #19: The Equal Employment Opportunity Regulation Certification includes a one field for the proposed subcontractor. If the Bidder has more than one proposed subcontractor, is the Bidder supposed to type in all the proposed subcontractors in the one field?
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:All proposed subcontractors should be included on one field.
Response posted 03/21/2022


Response #3:All proposed subcontractors should be included on one field.
Response posted 03/23/2022


Response #4:All proposed subcontractors should be included on one field.
Response posted 03/28/2022




Inquiry #20: Please confirm sump pumps do not require guide rails. Nothing mentioned on the drawings or in the specifications.
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:No guide rails are require. Please bid per the current contract document.
Response posted 03/17/2022




Inquiry #21: Can the 12" Corrugated High Density Polyethylene Pipe Conduit be installed by the use of Horizontal Directional Drill?
Inquiry submitted 03/15/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/15/2022


Response #2:No, directional drilling is not called out in the LADWP plans or specifications. There is no 12" conduit called out on the plans. Please bid per the current contract documents.
Response posted 03/17/2022




Inquiry #22: Refer to plan sheet 118 and notes 5 and 6. Please confirm the utility construction standards plan details and conduit size the contractor is to build this work.
Inquiry submitted 03/16/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/16/2022


Response #2:Per LADWP plans that will be provided during construction, “Customer to construct 2-4”P ED new conduits”. The developer shall contact the department’s electrical service representative (ESR) in area 210 at (310)552-1709 prior to start of construction. Customer shall provide a meter pedestal following guideline in the electrical service requirements manual, Page 2-44 through 2-46, and must be approved by ESR. Consult with the ESR for the meter pedestal orientation and specifications. All LADWP plans will be provided during construction. The two 4” conduits will be installed from pole to new service pedestal. Please bid per current contract documents.
Response posted 03/17/2022




Inquiry #23: “What is the concrete classification for Topping Concrete to be place on top of pump plant floor, as called out on sheet ST-4”
Inquiry submitted 03/18/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/18/2022


Response #2:The bid opening date is 3/22/2022 and it is unlikely that an Addendum will be issued . Please bid per the current contract bid documents.
Response posted 03/21/2022




Inquiry #24: Please confirm or verify Lighting Fixture Schedule and lighting controls or allowed fixture manufacturers.
Inquiry submitted 03/18/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/18/2022


Response #2:The lighting fixture schedule has to be created after the panelboard is installed and all the individual loads are connected to dedicated circuit breakers. Refer to 74-3.02C and and 74-3.02G for more information on lighting schedule and allowed fixtures. The lighting fixtures must comply with the specs in 74-3.02G.
Response posted 03/21/2022




Inquiry #25: The response to Inquiry #21 was that no directional drilling is called out in the LADWP plans. We are aware that this is not shown on the plans, but need clarification on how Caltrans wants this installed across the active roadway? Please advise open trench method or directional drilled?
Inquiry submitted 03/18/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/18/2022


Response #2:Open trench method. Conduits encased in 3" of concrete.
Minimum cover from top of concrete envelope to finished grades shall be 30" in paved areas and 36" in landscape areas.
Response posted 03/21/2022




Inquiry #26: On sheet #3 of the plan set per Section A-A, it appears that a new section of Jointed Plain Concrete Pavement is to be installed along the new Maintenance Vehicle Pullout area. What bid item is this section of JCP Pavement to be paid under?
Inquiry submitted 03/18/2022

Response #1:Your inquiry has been received and is being reviewed. Thank You for your patience.
Response posted 03/18/2022


Response #2:The Jointed Plain Concrete Pavement is part of the structural section “A” and is shown on the plans as an existing structural section that will be remove in order to place the new structural section “1” that consist of RUBBERIZED HOT MIX ASPHALT (GAP GRADED), HOT MIX ASPHALT (TYPE A), LEAN CONCRETE BASE and CLASS 3 AGGREGATE BASE.
Response posted 03/21/2022


The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.07, "JOB SITE AND DOCUMENT EXAMINATION" of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.