Viewing inquiries for 04-2Q7404

Submit new inquiry for this project


Inquiry #1: FYI-Caltrans to-All Bidders- How do I register for Mandatory Pre-Bid Meeting?
Inquiry submitted 04/28/2025

Response #1:Please do not use the Bidder Inquiry platform for Mandatory Pre-Bid Meeting registration; it is for inquiries related to bidding on the project contract. Register in advance of the Mandatory Pre-Bid Meeting, and no later than 1 hour before the meeting time, by sending an email with bidder information to D4.Construction.Duty.Senior@dot.ca.gov Please include the project number & "Mandatory Pre-Bid Meeting", within the subject of the email.
Response posted 04/28/2025


Response #2:Companies that attended the Mandatory Pre-Bid Meeting: • Aldridge Electric • Alfaro Communications Construction,Inc. • Anvil Builders Inc • Blue Arc Electric, Inc. • Bridge Masters Inc. • Horizonisp • Controls Systems Consulting Corp • Crosstown Electrical & Data, Inc. • DMZ Builders • Dynamic Generator Service, Inc. • HD Short Load LLC. • Macano Tech • MEL Electric, Inc. • MP Nexlevel • MP Nexlevel of California • Ollivier Corporation • PB Electric, Inc. •


PTM General Engineering Services Inc.
Purus Inc
S Kwok Engineers, Inc.
SECC Corporation

St. Francis Electric, LLC.

Studebaker Electric, Inc.

Teichert Energy & Utilities

Tennyson Electric

Veteran Pipeline Construction

Response posted 05/21/2025


Response #3:Companies that attended the Mandatory Pre-Bid Meeting: • Aldridge Electric • Alfaro Communications Construction,Inc. • Anvil Builders Inc • Blue Arc Electric, Inc. • Bridge Masters Inc. • Horizonisp • Controls Systems Consulting Corp • Crosstown Electrical & Data, Inc. • DMZ Builders • Dynamic Generator Service, Inc. • HD Short Load LLC. • Macano Tech • MEL Electric, Inc. • MP Nexlevel • MP Nexlevel of California • Ollivier Corporation • PB Electric, Inc. • PTM General Engineering Services Inc. • Purus Inc • S Kwok Engineers, Inc. • SECC Corporation • St. Francis Electric, LLC. • Studebaker Electric, Inc. • Teichert Energy & Utilities • Tennyson Electric Veteran Pipeline Construction •
Response posted 05/21/2025


Response #4:For the contact list, click on the link: http://website.dot.ca.gov/dist4/construction/contracts/04-2Q7404/MPBM%20Contact%20List%2004-2Q7404.pdf
Response posted 05/22/2025




Inquiry #2: Please provide clarification.

Installations throughout the Fiber Optic Electrical plans have multiple notes attached. Example being Note 7 and Note 101 show up together quite often as part of the same conduit run.

E-3 Note 7 states it is a 3" Conduit, but many of the same runs have Note 101 in conjunction with Note 7 and Note 101 states Install Conduit Trench Method (4-1.5" HDPE).

Looking at the quantity pages, it's not clear that this was meant for a conduit run to have both a 3" and 4-1.5" Conduits in the same trench or not. Is it Caltrans' intent that we should have both a 3" and 4-1.5" Conduits when these notes are shown together, despite the quantity pages not reflecting this?

Inquiry submitted 04/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/29/2025


Response #2:The intent is to install 3" conduit as specified in Note 7; Note 101 pertains only to the installation method. Detail 'TD' on drawing ED-1 illustrates the conduit layout.
Response posted 05/06/2025




Inquiry #3: Typically, Caltrans does not dictate the means and methods of a contractor's installation. This project though, is requiring specific methods of installation based on Caltrans' Notes. This includes Trenching, Boring, Trenching in Pavement. Is the Contractor allowed to deviate from this? If we would rather bore a section called out to be trenched would this be allowed or are we required to follow the plan Notes dictating our installation methods?
Inquiry submitted 04/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/29/2025


Response #2:Refer to section 4-1.07B "Value Engineering Change Proposal," of the Standard Specifications. Proposals for modifications to the contract documents may be submitted to the Engineer after contract award. Please bid per current contract documents.
Response posted 05/06/2025




Inquiry #4: The Backfill requirements for Trenching and for Trenching in Pavement call for Red Minor Concrete Backfill. Past Caltrans projects have only required Slurry Backfill for Trenching in Pavement and typically Native Backfill for Trenching in Dirt. This is an excessive cost for the project. Would Caltrans please consider changing this backfill requirement to Red Colored Slurry instead of Minor Concrete?
Inquiry submitted 04/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/29/2025


Response #2:Please bid per current contract documents.
Response posted 05/06/2025




Inquiry #5: Can you provide voltage and amps for CMS at location 116, shown on E-236?
Inquiry submitted 04/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/30/2025


Response #2:The CMS sign will operate on 120 or two legs of 240V(ac) single phase at 60 Hz. It shall have a max power consumption of 4,000 W. Refer to Caltrans Spec for CMS System TEES Ch 8. Location 116 is Type 1 or model 500.
Response posted 05/06/2025




Inquiry #6: Can you confirm amps for CMS at location 117, shown on E-237? Is 80A correct?
Inquiry submitted 04/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/30/2025


Response #2:The CMS sign will operate on 120 or two legs of 240V(ac) single phase at 60 Hz. It shall have a max power consumption of 4,000 W. Refer to Caltrans Spec for CMS System TEES Ch 8. Location 117 is Type 2 or model 510.
Response posted 05/06/2025




Inquiry #7: Can you clarify if CMS at location 117 (E-237) will be retrofitted to existing structure? Or will new structure plans be provided?
Inquiry submitted 04/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 04/30/2025


Response #2:Contractor to replace old CMS with new CMS on existing structure.
Response posted 05/06/2025




Inquiry #8: Sheet SD-1 and PD-1 (Sheet 368 of 666) calls out this sign structure to be new and notes to see structural sheets however no structural sheets exist for the design of this structure (post heights, truss type, post types etc...) Please provide design details. Bid Item 0030 has a pay weight of 45,752 LBS which we assume is for this new sign structure however it is not clear if all of this pay weight is for this structure or not?

Inquiry submitted 05/07/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/08/2025




Inquiry #9: Please clarify if a traffic control supervisor is required. There is mention of a TC supervisor in Special Provisions section 12-4.02C(13), but there is not a bid item for the TC Supervisor.
Inquiry submitted 05/08/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/09/2025




Inquiry #10: Please clarify what the plant establishment period is. Nothing is mentioned in the Notice to Bidders
Inquiry submitted 05/08/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/09/2025




Inquiry #11: Please Confirm that Caltrans wants the Contractor to Remove 4 Video Cables, and a 50 Pair SIC Cable Per E49 and that this is not just taken from an old standard - If these are to be removed, are these tied down in any way? Or Anchored in? If so, what is the spacing of these and does this run through the entire stretch of the Bay Bridge? If not, what footage is to be removed.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025


Response #2:Yes, the Contractor is to remove 4 video cables and 50 pair #19 cable per Detail B on sheet E-49. This detail is from an as-built per Contract No. 040804, so the Contractor is to field verify if/how the communication cables are tied down or anchored. These cables run throughout the entire west span of the Bay Bridge (Section A-A is shown from sheets E-49 to E-56).
Response posted 05/20/2025




Inquiry #12: E45 Conduit run shows Trenching 4 - 1.5" Conduits in dirt, then without any type of transition, it becomes Install Conduit on Structure (Note 104 and 105 on E46). Additionally, the majority of the structure runs fail to identify the size of the conduit to be installed on the structures. Please provide transition details for this run and clarify for the entire project what size conduit is to be installed where it calls out to be placed on structures.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025




Inquiry #13: If notes 101, 102, 103 and 104 are only meant to callout the installation methods and not the size of the conduit as you described in response to inquiry #2, then what is the Contractor to do when, for example Note 102 and Note 105 appear together (See E66). The Quantity page shows a 4" Conduit being installed, but none of the notes actually call for this. Please update and clarify these notes, if notes 101 through 104 are truly only for method of installation then they should not state anything about 4-1.5" Conduits as this is very confusing when no other notes state what size conduit to install, but your quantity pages state install a 4" Conduit. Please correct your Notes.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025




Inquiry #14: Please confirm that both construction notes on sheet E-45 (sheet 422) are supposed to be 104 and 105. One shows construction note 101, but that doesn't make sense and next sheet shows note 104.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025




Inquiry #15: Please confirm that const note 133 on sheet E-48 (fiber across Harrison St) should be const note 134.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025




Inquiry #16: Please clarify that const note 101, furthest to the right on sheet E-69, should be const note 104.
Inquiry submitted 05/12/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/12/2025




Inquiry #17: Please confirm that construction note 101 on sheet E-120 should be construction note 102 instead, as it is shown inside the barrier, on the roadway. Or alternatively, please clarify if new fiber optic line should be moved south behind the barrier, and installed in the dirt.
Inquiry submitted 05/13/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/13/2025




Inquiry #18: Please clarify if there is a difference between construction note 3, and construction note 104, regarding the installation of conduit to existing bridges or structures. Additionally, please clarify if the first column of the quantity table sheets EQ-3 to EQ-6 (Conduit Installation on Structures) applies to both construction notes 3 and 104, or only one of them. If it only applies to one construction note, please consider adding an additional column to the tables, and / or reconciling the quantities.
Inquiry submitted 05/14/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/14/2025


Response #2:There is a difference between construction notes 3 and 104. Construction note 3 refers to conduit installation on bridge and note 104 refers to conduit installation on structure. The first column on sheets EQ-3 to EQ-6 only apply to construction note 104. Please note that the quantities on sheets EQ-1 to EQ-11 are for reference only. Contractor shall conduct quantity takeoffs and verify based on the plan sheets.
Response posted 05/16/2025




Inquiry #19: Per the electrical systems quantities sheets, there are significant differences in the quantities shown on the plan sheets (E-10 to E-168) compared to what is shown in the quantity tables. The quantity tables are missing many sheets – for example sheet EQ-3 does not include sheet numbers E-10 through E-43, E-70 through E-93, and sheet EQ-5 does not include sheet numbers E-142 through E-147. Sheets EQ-1 and EQ-2 appear to be missing many sheets as well. This is resulting in takeoff quantities significantly overrunning what is shown in the quantity tables on sheet EQ-6 – for example, there is approx. 700% more horizontal directional drilling (HDD) and 200% more trenching in dirt than what is reflected on the summaries shown on sheet EQ-6.
Please revise the quantity tables to accurately reflect the plans.

Inquiry submitted 05/14/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/14/2025


Response #2:For quantity summaries of sheets E-10 through E-43, E-70 through E-93, and E-142 through E-147, please refer to sheets EQ-1 and EQ-2. The quantity summaries of sheets E-44 through E-69, E-94 through E-141, and E-148 through E-168 are summarized in EQ-3 through EQ-6.
Please note that the quantities on sheets EQ-1 to EQ-11 are for reference only. Contractor shall conduct quantity takeoffs and verify based on the plan sheets.
Response posted 05/16/2025




Inquiry #20: The trench backfill calls for Red Color Minor concrete. It’s understood that colored concrete encasement is for the protection of the conduits containing fiber optics cable in areas with future possibility of excavations. Although Minor concrete wouldn’t setup fast enough to pave over it or backfill in the same shift. Since leaving a trench open to live traffic is not an option. Would Caltrans issue an amendment changing this requirement to Rapid setting slurry/concrete?

Rapid setting slurry/concrete would achieve strength fast enough to provide for back filling or paving in the same shift but its not part of the scope.

Inquiry submitted 05/15/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/16/2025




Inquiry #21: It appears there are some missing pullboxes shown on each side of the HDD location shown on sheet E-65. Please clarify.
Inquiry submitted 05/19/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/19/2025




Inquiry #22: Is it possible to release the digital files for these plan sets?
Inquiry submitted 05/19/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/19/2025


Response #2:No, the plan set digital files won’t be released for this project. All the available Supplemental Project Information is listed in 2-1.06B.
Response posted 05/19/2025




Inquiry #23: Given the highly variable nature of the existing pavement sections, it follows that the difficulty of trenching, potholing, and any other required excavation in pavement will also vary greatly. Can you please provide existing pavement sectional details?
Inquiry submitted 05/22/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/22/2025


Response #2:Please refer to the typical cross section information provided in sheets X-1 and X-2.
Response posted 06/06/2025




Inquiry #24: With regards to the Micro-trenching for the City of Oakland, currently, the max width on a Micro-trencher is 3". The detail shown on ED-2 Detail D shows a width of nearly 3.75" (once you factor in the OD of the 1.5" conduit and add the 1" spacing on each end) being needed. Please provide a new detail that will allow for Micro-trenching on this project so that spacing plus OD will equal 3".
Inquiry submitted 05/22/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/22/2025




Inquiry #25: Due to the high variability of paving section thickness and composition throughout the project area and the subsequent variable effect that it will have on all excavation activates, can you please release information on the existing paving sections?
Inquiry submitted 05/22/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/22/2025


Response #2:Please refer to the typical cross section information provided in sheets X-1 and X-2.
Response posted 06/06/2025




Inquiry #26: The Fiber Optic Cable Systems "E Sheets" show the path for the fiber optic cable system. When the "E Sheets" are cross referenced to "Bridge Table No. 1 & No. 2" there is confusion regarding whether or not there is bridge or structure attached conduit.

For example; Colma Creek 35-0118, South SF Belt Railway OH 35-0121, & South SF OH 35-0094R do not have callout 3 or 54 on the "E sheets" (Indicating structure attached conduit is to be installed) but the bridge table & detail callouts (page 4&5 of 15) show attachment details for those structures.

Does the "General Plan" Pages 652-66 or Sheets 1-15 supersede the conduit path drawings? Please clarify if there are a total of 40 structures/bridges that will have a 4" conduit attached referencing the information contained in sheets 1-15 (or pages 652-666) on the "general plan" or if the "E sheets" should be used for the quantity takeoffs, effectively eliminating some structures/bridges?

Inquiry submitted 05/22/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/22/2025


Response #2:Please use "E sheets" for quantity takeoffs. The Bridge Tables on pages 653-654 show both existing and proposed conduit. These pages are for reference only on where the new or existing conduit is attached.
Response posted 05/29/2025




Inquiry #27: There are two callouts associated with the structure/bridge attached conduit. Callout 3 and callout 104. Callout 3 is "install conduit to exist bridge structure" Callout 104 "Install conduit on structure."

The "EQ Electrical Systems quantities" sheets quantify these callouts as:
Callout 3- 1-1/2" Type 1 Conduit
Callout 104- Conduit installation on structures

What detail should be used for callout 3? (I am assuming it is a run of 3ea-1-1/2" conduits based on LF quantities)

Do the details shown in the "general plan" (Sheets 1-15) apply to both callout 3 & 104?

Inquiry submitted 05/22/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/22/2025


Response #2:In general, Note 3 only specifies to install conduit on the structure. It should be accompanied by other notes such as Note 54 which calls out what to install. In this case, Note 54 calls to install four 1-1/2" type 1 conduit. The quantities shown on the quantity sheet should reflect the total length of conduit.
Response posted 06/02/2025




Inquiry #28: There are multiple locations that require concrete / pavers / slope paving removal and restoration for installation of the pullboxes and vaults (see sheets E-12, E-34,E-44, E-48, E-123, E-124, E-164 to E-168, etc.) Please clarify under what bid items the following items of work shall be paid, and consider providing construction details or quantities for the new concrete sidewalk / curb ramps so that contractors can understand how much hardscape they will be asked to replace.
1. Remove Concrete (typically there is a bid item for this?)
2. Remove Pavers
3. Remove Slope Paving
4. Surface Restoration for Concrete / Pavers / Slope Paving.

Inquiry submitted 05/23/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/23/2025


Response #2:The bid item is represented by the title of the sheets. For example, sheet E-47 is titled "FIBER OPTIC CABLE SYSTEMS" so all work shown on E-47 should be under the bid item of the same name.
Response posted 05/29/2025




Inquiry #29: It appears there are a few locations where new fiber optic conduit and pull boxes are required within fenced in areas. Will Caltrans be removing and replacing fences as needed for access to these areas? Can Caltrans provide bid item(s) for this work if they are not going to handle the removal and re-installation of fencing?
Inquiry submitted 05/23/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/23/2025


Response #2:Please provide specific locations where this inquiry applies.
Response posted 06/06/2025




Inquiry #30: Please provide a detail or more information regarding how the pavement will be removed and replaced around the pullboxes located in asphalt, along the freeway. Will the AC section be removed and replaced as needed for construction, and perhaps a larger area be milled and overlaid?
Inquiry submitted 05/23/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/23/2025




Inquiry #31: The erosion control plan sheets show fiber roll and RECP at some of the wood mulch areas, but there aren't any bid items for these two scopes of work. Please clarify if fiber roll and RECP are required, and under which bid item they shall be paid.
Inquiry submitted 05/23/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/23/2025




Inquiry #32: There is not any lane closure charts or traffic control sheets for sheets E-65 to E-69 for trenching along the Bay Bridge trail. Please provide lane closure charts, closure and detour information, or additional information so Contractor can understand what traffic control will be required in this area.
Inquiry submitted 05/27/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/27/2025


Response #2:This is a Caltrans maintenance road, so lane closure charts are not necessary. Coordination with the Resident Engineer is required for closures in this area.
Response posted 06/06/2025




Inquiry #33: Please provide a closure chart for the NB 880 offramp to Oak Street.
Inquiry submitted 05/27/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/27/2025


Response #2:This is already provided as Chart No. J46, "NB 880 Off-Ramp to Oak St/6th St.
Response posted 05/29/2025




Inquiry #34: Please confirm that this project is federally funded and that Buy America applies to this project.
Inquiry submitted 05/27/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/28/2025


Response #2:Yes, this project is federally funded and Buy America applies.
Response posted 05/29/2025




Inquiry #35: Please confirm that Contractor does not have any QC responsibilities for the trenching and backfilling, including minor concrete or slurry backfill, or native backfill.
Inquiry submitted 05/27/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/28/2025


Response #2:Please follow all project documents (Standard Specifications, Special Provisions, Contract Plans, Standard Plans, etc) for trenching and backfilling operations.
Response posted 05/29/2025




Inquiry #36: To clarify, your answer to inquiry #11 suggests that the removal of any potential ties or anchors would be CCO work. Given that Caltrans has no information on how these cables are secured or the spacing associated with this and the fact that Caltrans wants the contractor to investigate it to determine what is needed, makes this work an unknown to the contractor that can not be bid properly since Caltrans lacks the information needed. Please confirm that this would be CCO work.
Inquiry submitted 05/28/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/28/2025


Response #2:For the trunk line, the cables should only be tied at the towers (6 towers) and mounting locations. The rest is not tied.
Response posted 06/06/2025




Inquiry #37: Due to the absence of bore logs to determine the presence of ground water, and the design of the trenching and horizontal directional drilling details provided, we are assuming there will not be ground water present. Please confirm this is correct.
Inquiry submitted 05/28/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/28/2025




Inquiry #38: Can Caltrans please release bore logs for this project?
Inquiry submitted 05/28/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/28/2025




Inquiry #39: Please reference Sheet ED-1, Detail FC, Type A. The four each HDPE innerducts do not fit inside the 4" conduit. The OD of 1.25" innerduct is roughly 1.66" and the ID of the 4" conduit is nearly 4", max, depending on conduit type. Please allow or type B to be utilized (1.5" SCH 80 conduits wrapped in a cable tie), for both trenching in pavement, and trenching in dirt.

If there is an area where 4" conduit is required, please upsize the conduit so that innerduct will fit,

Inquiry submitted 05/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/29/2025




Inquiry #40: Please clarify what type of conduit is required for the 4" conduit shown on the plans. Is this supposed to be a type 3 conduit as well? Additionally, the 4 ea 1.25" innerducts do not fit inside a 4" pipe. Please clarify.
Inquiry submitted 05/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/29/2025




Inquiry #41: The quantity tables on sheet EQ-3 through EQ-6 show a 4" conduit for a total quantity which matches the summary of the quantities for trenching in dirt plus trenching in pavement plus HDD. Clearly, this is incorrect since the trench in pavement does not require 4" conduit; per detail TP on ED-1, they are wrapped in a cable tie, not 4" conduit. Please revise the 4" conduit quantities as they are causing significant confusion.
Inquiry submitted 05/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025


Response #2:Please note that the quantities on sheets EQ-1 to EQ-11 are for reference only. Contractor shall conduct quantity takeoffs and verify based on the plan sheets.
Response posted 06/18/2025




Inquiry #42: Please clarify what material is required for minor concrete or slurry backfill for the trenches.
Sheet X-1 shows "slurry concrete". Sheet ED-1 and ED-2 show "minor concrete".

Inquiry submitted 05/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #43: Please confirm that tree removal will not be required as part of this project, and if trees are required to be removed, it will be paid as a change order. It appears there is a significant amount of trees within / near the alignment along highway 101.
Inquiry submitted 05/29/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #44: Fiber Optic Notes and Cable Types: Looking at the plans the notes change from 288-strand SMFO cable, to Type 1, 288 SMFO optic cable to Type 4 - 288 SMFO cable. I am not seeing any differential in the specs between the standard and the Type1 & Type 4 288 SMFO cable. I know that MMBN specs type 1 & type 4 which is a ribbon style fiber optic cable. Are we using a ribbon style cable where it says type 1 or type 4 and a standard loosetube cable where it does not note type 1 or type 4?
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #45: Fiber Optic Splice Cases: I am seeing in the Fiber optic qty sheets there are "outdoor fiber optic splice closures" and "splice closures (type1)" called out. I am not seeing in the specs where it differentiates between the two types of splice cases. Is there a difference between the two cases?
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #46: On Sheet 360 (THQ-1) of the plans, it is showing Temporary Delineator (Class 1) “1,149 Each”, however there is no bid item for them. Please provide a bid item for the Temporary Delineator (Class 1).
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #47: Bid Item #15 – Temporary Silt Fence 13,700 LF is provided for bidding, however the details in Sheet 372-377 (LD-1, ECL-1, ECD 1-3 & ECQ-1) of the plans, shows fiber rolls. Please clarify if its silt fence or fiber rolls.
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #48: On sheet 376 (ECD – 3) of the plans, it is showing to install RECP (netting) at the cut/fill-slope locations where the new vaults are to be placed, however, there is no bid item for this. Please provide a bid item for the RECP (Netting).
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025




Inquiry #49: Per Section 5-1.50 PHOTO IDENTIFICATION of the Special Provisions, is states “Furnish Photo Identification (ID) system and issue photo ID cards to all job site personnel.” Is this required?
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 05/30/2025


Response #2:Yes, Section 5-1.50 PHOTO IDENTIFICATION of the Special Provisions needs to be followed because work will be done on critical bridges.
Response posted 06/18/2025




Inquiry #50: Per Section 12-4.02C(13) TRAFFIC CONTROL SUPERVISORS, it states to provide a traffic control supervisor anytime when work is being performed. However, under 12-4.02(13)(d) Payment, it states that “The Traffic Control Supervisor is paid for each day.” Please provide a bid item for the Traffic Control Supervisor.
Inquiry submitted 05/30/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/02/2025




Inquiry #51: Per ED-6, contractor is to label each new and existing cable in each pull box, vault, and cabinet. Correctly labeling each unlabeled existing conductor found in every pull box, vault, and cabinet will require extensive research of the existing systems. The extent of this research is unknown and cannot be accurately quantified. Can the contractor use ED-6 labeling direction on only new conductors and disregard existing conductors in an attempt to avoid inflating the total estimate unnecessarily?
Inquiry submitted 06/02/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/02/2025


Response #2:Yes, the Contractor may use ED-6 labeling direction on only new conductors and cables in each pull box, vault, and cabinet.
Response posted 06/13/2025




Inquiry #52: Per ED-6, contractor is to label each new and existing cable in each pull box, vault, and cabinet. Correctly labeling each unlabeled existing conductor found in every pull box, vault, and cabinet will require extensive research of the existing systems. The extent of this research is unknown and cannot be accurately quantified. Can the contractor use ED-6 labeling direction on only new conductors and disregard existing conductors in an attempt to avoid inflating the total estimate unnecessarily?
Inquiry submitted 06/02/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/02/2025




Inquiry #53: Please clarify where the Type C Flexible Innerduct shown on sheet ED-1 applies. There aren't any construction notes which call for type 3C (flexible innerduct). Is this required in every place there is 3" conduit, or is it not required anywhere?
Inquiry submitted 06/02/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/03/2025


Response #2:Contractor shall use plan sheets for quantity takeoffs and construction work. Detail FC Types A, B, C are typical Caltrans specs that are provided for reference only.
Response posted 06/13/2025




Inquiry #54: Where do contractors submit the required 5-DAY DBE commitment, confirmation, and GFE documentation?
Inquiry submitted 06/03/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/03/2025


Response #2:Per the Electronic Bidding Guide, submit the DBE submittal and the Off-Road Deisel Vehicle List form to the Office Engineer. The address is shown in the Electronic Bidding Guide and Section 1-1.11 of the Standard Specifications. Per the Electronic Bidding Guide, either submit an electronic bid bond with your bid or submit a paper bid bond to Office Engineer prior to the specified bid opening date and time.
Response posted 06/04/2025




Inquiry #55: Bid Items # 27 is for 10 Move-In/Move-Out (Erosion Control), however there are no permanent erosion control Bid Items listed. Perhaps this relates to RFI # 48 and the RECP Netting shown on ECD-3 AND Bid Item # 25 - 2,720 CY Wood Mulch? Please clarify.
Inquiry submitted 06/03/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/03/2025




Inquiry #56: Please provide a list of the Caltrans approved material suppliers for conduit materials as shown on detail sheet ED-1
Inquiry submitted 06/04/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/05/2025


Response #2:Please refer to the Standard Specifications and Special Provisions for the conduit specifications. There are no Caltrans approved suppliers for conduits.
Response posted 06/05/2025




Inquiry #57: Given how many unanswered questions remain, can Caltrans please push the bid date back by 3-4 weeks so that when the questions are eventually answered, the contractor will have enough time to correctly bid the project?
Inquiry submitted 06/05/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/05/2025


Response #2:The bid open is expected to be delayed at least three weeks. Official notice of bid open delay is provided through addendum only.
Response posted 06/05/2025




Inquiry #58: Per Bid Item #1 – POSITIVE LOCATION OF EXISTING UNDERGROUND INFRASTRUCTURE – 800 each, please provide whether the pothole is in concrete, AC Pavement or native material, so we can accurately price out any preparatory demolition that needs to be perform before potholing and what needs to be patched back, after potholing.
Inquiry submitted 06/05/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/05/2025




Inquiry #59: Please provide a foundation detail for the structure / bridge mounted poles called out by construction note 165 and 171 on sheet E-234. The details called out in the plans do not apply. Are the poles supposed to be bolted directly to the bridge, or will the barrier rail be removed / replaced with a thicker barrier rail that can accommodate the poles?
Inquiry submitted 06/05/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/06/2025




Inquiry #60: Plan sheet E-234 shows a "R" (Rigid) conduit going across 5th street to the new Type 3 service enclosure. It appears that this ~50' section of pipe should not be rigid, but should be underground with either HDD, or trenching. Can you confirm this should be completed by HDD? Or if it shall be trenched, then what trench restoration detail shall apply?
Inquiry submitted 06/05/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/06/2025


Response #2:The callout "R" refers to "conduit or structure attached to the structure or service pole" per Caltrans Standard Plan ES-1B.
Conduit run 9 shall be completed by directional boring. For the conduit type and specifications, the contractor shall coordinate with PG&E.

Response posted 06/13/2025




Inquiry #61: Inquiry #8 has not been answered and we need adequate time to quote this - is the project going to be postponed so #8 can be addressed?

Inquiry submitted 06/06/2025

Response #1:The bid open is expected to be delayed at least three weeks. Official notice of bid open delay is provided through addendum only.
Response posted 06/06/2025




Inquiry #62: Per plan sheet CS-1, the table shows a total of 36 signs each, for sign numbers A & B. The plan sheet only shows a total of 19 each. For sign numbers A & B, please clarify if Contractor should include 19 each as shown, or a total of 36 each (at locations to be determined in the future).
Inquiry submitted 06/09/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/09/2025


Response #2:Assuming the inquiry is about signs A and C, not A and B. The Contractor should include 19 each of signs A and C.
Response posted 06/18/2025




Inquiry #63: Please provide trench details or additional clarity regarding the different types of trenching required for the below grade conduit installation required for Modifying Camera Systems (E-183 to E-203), Modify Traffic Monitoring Stations (E-204 to E-230), and Modify Ramp Metering (E-231 to E-235). The plans only call out a conduit size, but don't refer you to the trench details. It seems that maybe a smaller / different trench detail would be required for this work.
Inquiry submitted 06/09/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/09/2025




Inquiry #64: Sheet MIQ-3 shows a total of 76 EA PCMS signs, but bid item 10 shows a quantity of 50 EA PCMS signs. Please clarify.
Inquiry submitted 06/13/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/13/2025




Inquiry #65:
Can two subcontractors be listed for the same or similar type of work on the same bid item number? Can two subcontractors be listed for the same or similar type of work on different bid line items?

Inquiry submitted 06/18/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/18/2025




Inquiry #66: Can the prime contractor list multiple directional drilling subcontractors on the same bid item?
Inquiry submitted 06/18/2025

Response #1:The inquiry has been received and submitted for consideration.
Response posted 06/19/2025


The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.07, "JOB SITE AND DOCUMENT EXAMINATION" of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.